ID
Icons
Message
Cause/Action
197
CH2 cable break
Check current output cable connection. Passive operation:
check external power supply.
198
CH2 output frequency too
low
The process value is below the parameter 'Lower range
value'. The output frequency cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
199
CH2 output frequency too
high
The process value is above the parameter 'Upper range
value'. The output frequency cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
200
CH2 pulse overflow
Pulse output has insufficient pulse separation. Increase
Amount per pulse, or reduce Pulse width, or reduce Pulses
per amount.
201
CH3 loop current in lower
saturation
The process value is so low that the loop current reaches
the lower saturation limit and cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
202
CH3 loop current in upper
saturation
The process value is so high that the loop current reaches
the upper saturation limit and cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
203
CH3 cable break
Check current output cable connection. Passive operation:
check external power supply.
204
CH3 output frequency too
low
The process value is below the parameter 'Lower range
value'. The output frequency cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
205
CH3 output frequency too
high
The process value is above the parameter 'Upper range
value'. The output frequency cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
186
Operating Instructions, 01/2019, A5E44030648-AB