NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper
mounting.
● Before installing ensure there is no visible damage to the device.
● Make sure that process connectors are clean, and suitable gaskets and glands are used.
● Mount the device using suitable tools. Refer to the information in Technical data
(Page 195).
4.2
Installation instructions
4.2.1
Transmitter installation
CAUTION
Opening lid
Care must be taken when opening the lid to avoid the lid falling.
Note
Hygienic applications
If the device is wall or pipe-mounted in a hygienic application, always use domed nuts.
4.2.1.1
Remote field mount
Mounting on wall
1. Prepare holes with aid of mounting bracket, see Mounting bracket dimensions (Page 223).
2. Fasten mounting bracket with black cushion pad to wall (torque 10 Nm).
Installing/mounting
4.2 Installation instructions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
41