Description
Torque (Nm)
Transmitter pedestal lock screw
Compact version:
10
Remote version:
6
Pedestal lock screw cap
10
Cable gland to housing (Siemens supplied, metric)
10
Note
NPT glands
When using NPT glands, the user must take care to use the supplied NPT thread adaptors.
11.6.1
Sensor design
Description
Specification
Dimension and weight
See "Sensor dimensions" (Page 217)
Process connectors
● EN1092-1 B1 PN16, PN40
● EN1092-1 B2 PN63, PN100
● EN1092-1 D (gasket groove), PN40
● ASME B16.5 RF, Cl 150, Cl 300, Cl 600, Cl 900, CI1500
● ISO 228-1 G *
● ASME B1.20.1 NPT *
● DIN 11851 Hyg. Screw **
● DIN 32676 (ISO) Clamp Row B *
● SMS1145 - Hyg. Screwed
● JIS B 2220, 10K, 20K
● EN 1092-1 PN 16, PN40, NAMUR length
Electrical connection
● M12 connector with 4-wire cable
● Standard cable with polymer / brass / stainless steel cable
glands (metric or NPT)
● Armored cable with stainless steel armored cable glands
(metric or NPT)
● Conduit entries (metric or NPT)
Material
Measuring tubes
● AISI 316L / EN1.4404
● C4 (2.4610) nickel alloy or C22 (2.4602) nickel alloy
Process connectors
● Standard:
– AISI 316L / EN1.4435 or EN1.4404
– C4 (2.4610) nickel alloy or C22 (2.4602) nickel alloy
Sensor enclosure
Stainless steel 1.4404 (AISI 316L), 1.4301 (AISI 304), 1.4308
(ASTM CF8)
DSL enclosure
Aluminum with corrosion-resistant coating
Technical data
11.6 Construction
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
201