Siemens AG 6SE8004-0BH76
SIMOVERT MV Commissioning Instructions
49
4.2
Start-up steps
4.2.1
Configuration word
The drive converter type which is being used must be set using the KONFIG.X
configuration word in the FP-IO. This is also used to define whether the Profibus
interface is used.
6LJQLILFDQFHRI.21),*;
Bit 0 :
0
with Profibus communications
1
without Profibus communications
IDFWRU\VHWWLQJ
1RWH
When using the Profibus interface, bit 0 must be set to 0!
Bit 1 :
0
Drive converter with air cooling
Bit 4 :
1
Sinusoidal filter
4.2.2
Checking the protective functions
The internal protective functions, door limit switches, installation monitoring,
contact MM3 (A200-D03-X3), safety shutdown (door) must be checked. This is
best realized by initiating the particular function and checking the shutdown (trip)
on the display of the OP2 operator panel. Further, the protective functions can also
be monitored via the LED display of the SUL. A high signal (LED is lit) which
indicates that the function to be monitored is OK. The binary inputs and outputs of
the SUL module are assigned as follows for the drive converter:
%LQDU\LQSXW
/('
BE 1
H5
fan (Q150, Q151, Q152, Q153), differential pressure monitoring
(B80) and internal cabinet temperature monitoring A880
BE 2
H6
m.c.b.’s of the power supplies (F120, F130, F160) and SIMADYN-D
power supply monitoring
BE 3
H7
SIMADYN-D power supply fans (A200-G1)
BE 4
H8
Safety circuit (safety shutdown (S10), door limit switches (S1 to S9),
contact MM3 (A200-D03-X3), external safety trip)
BE 5
H9
Ground fault monitoring (B190)
BE 6
H10
GSV 55 V / 100 kHz (G90), m.c.b. Q90
%LQDU\RXWSXW
/('
BA 1
H11
This issues a signal to start pre-charging. This signal is output from
the IUU module in the SPV function package in the SIMADYN-D
configured software.
BA 2
H12
Issues the enable signal, CLOSE circuit-breaker. This enable signal
is dependent on the following conditions: The SUL power supply
must be greater than 17 V to 19 V, the telegram data transfer to ISL
must be OK (yellow LED), it is
QRW
permissible that the crowbar
thyristor is ON, binary input 4 (safety circuit) must be high. If one of
these conditions is not fulfilled, then the circuit-breaker CLOSE can
only be re-enabled by removing the cause of the failure and
ACKNOWLEDGING at the drive converter (LP or terminal strip).