SIMOVERT MV Commissioning Instructions
0RWRUQRORDGFKDUDFWHULVWLF
The no-load characteristic values can be taken from the motor data sheet.
250
200
150
100
50
0
A
No-load current
0
0,2
0,4
0,6
0,8
1,0
1,2
U
0
/U
N
[%]
i3 = 1.0 (176 A)
u3 = 1.0
i2 = 0.71 (125 A) u2 = 0.8
i1 = 0.48 (85 A)
u1 = 0.6
The values which have been determined, are entered at the IMU block in function
package TRV.
P740
IMU.U1 = u1
8
Coefficient of the magnetizing characteristic for
the per unit induced voltage
P743
IMU.S1
= i1
6
Coefficient of the magnetizing characteristic for
the per unit magnetizing current
P741
IMU.U2 = u2
8
Coefficient of the magnetizing characteristic for
the per unit induced voltage
P744
IMU.S2
= i2
6
Coefficient of the magnetizing characteristic for
the per unit magnetizing current
P742
IMU.U3 = u3
8
Coefficient of the magnetizing characteristic for
the per unit induced voltage
P745
IMU.S3
= i3
6
Coefficient of the magnetizing characteristic for
the per unit magnetizing current
If there is no motor data sheet, and field-weakening is not required, then no
adaptation is required.
The characteristic is linear with the factory setting:
P740 = P743 = #0,4
P741 = P744 = #0,6
P742 = P745 = #1,0
'ULYHFRQYHUWHUUDWLQJSODWH
The following values are determined from the drive converter rating plate, and are
entered at the DP block in function package TRV:
P609
DP.UDI
8',
Rated DC link voltage [V]
P608
DP.FMX
)0;
Maximum output frequency [Hz]
([DPSOH