6HOHFWHGIXQFWLRQV
Siemens AG 6SE8004-0BH76
SIMOVERT MV Commissioning Instructions
35
$FWLYDWLQJWKHIODVKIXQFWLRQ>)/$6+@
The output relay K1/K2 and the associated signaling LED can be switched to flash
(1 Hz clock frequency).
Flash OFF
= K1 and K2 not flashing
Flash K1
= K1 flashing, K2 not flashing
Flash K2
= K2 flashing, K1 not flashing
Flash K1/K2
= K1/K2 flashing
2XWSXWUHOD\VLJQDOIRUWKHIXQFWLRQWHVW>5(/$<7(6721@
In this menu, the output relay switching can be disabled for a function test (= relay
test : OFF).
5HVSRQVHGHOD\RQ>7,0('(/$<21@
In this menu, a response delay can be activated for the output relay. This setting is
only possible, if the A-ISOMETER was set to the dissymmetry or DC voltage
superimposition measuring technique. The selected response delay only acts on
the alarm stages with this measuring technique, and is added to the response time.
6HWWLQJWKHUHVSRQVHGHOD\>7,0(W V@
If the response delay is active, the appropriate time can be set here.
6HWWLQJWKHOLQHVXSSO\GLVFKDUJHFDSDFLWDQFH>&(0$;@
The A-ISOMETER can be adapted to the max. line supply discharge capacitance
in this menu (max. 500 µF). Please note, that for the setting C
E
= 500 µF, the basic
measuring time is increased to approx. 15 s
$FWLYDWHSDVVZRUG>3$66:25'2))@
A “Password" interrogation can be activated in this menu. This allows the A-
ISOMETER to be protected against unauthorized changes to the settings.
(QWHUSDVVZRUG>1(::25';;@
A new password can be entered in this menu. The password is only saved after an
acknowledgement using a password interrogation.
5(6(7IRUWKHEDVLFVHWWLQJ>5(6(7><1@1@
All settings can be reset to the factor setting in this menu.
'LVSOD\VRIWZDUHYHUVLRQ>62)7:$5(9;;;@
The software version is displayed on the LCD in this menu.