SIMOVERT MV Commissioning Instructions
4.3
Parameterizing the Transvektor closed-loop control
4.3.1
Determining the parameter data
The following are required to parameterize the closed-loop control:
1. Motor rating plate data
2. Motor equivalent circuit diagram data
3. Motor
no-load
characteristic
4. Rating plate data of the SIMOVERT MV
5. Speed
encoder
data
0RWRUUDWLQJSODWHGDWD
Rating plate data
H[DPSOH
P
N
2600 kW
U
N
3300 V
I
N
553 A
I
0
176 A
cos
ϕ
N
0.85
f
N
50 Hz
n
N
995 RPM
The following values are determined from the motor rating plate data and are
entered at the DP block in function package TRV:
6 kV
6,6 kV
P604
DP.RCM
5&0
= I
N
* 2,61
= I
N
* 2,87
P603
DP.RVM
590
= U
N
/ 2,61
= U
N
/ 2,87
P605
DP.CFN = cos
ϕ
N
&)1
Nominal power factor [-]
(0.85)
P606
DP.RSM = n
N
560
Rated motor speed [RPM]
(995 RPM)
P607
DP.RFM = f
N
5)0
Rated motor frequency [Hz]
(50 Hz)
P622
DP.PP
= Motor pole pair number
(3)