SIMOVERT MV Commissioning Instructions
69
4.3.8.6
Setting the closed-loop current control and switching frequency
P800
2.TRV.ISR10.X1
0.2
P816
2.TRV.ISQ.NQG
0.4
P847
2.TRV.ST50.FSC
800
4.3.8.7
Checking the motor flux and -voltage
&KHFNLQJWKHPRWRUIOX[DQGYROWDJHZKHQWKHGULYHLVXQGHUORDG
The IMOA.PIM and UMOD.PUM values in the FP-TRV, when the drive is under
load (optimum at the rated torque), should approximately correspond to the values
when the motor is running under no-load conditions (± 2 - 3 %). The influence of
the load on the voltage model flux can be minimized in operation using
UMOD.EXS / P770.
&KHFNLQJWKHPRWRUYROWDJH.3:<%
The value should increase from approx. 97 % under no-load conditions to approx.
100 % at rated speed and rated torque.
4.4
Overview of the software
The drive is parameterized using the start-up program of the SIMADYN Tele-
master. It is connected at the interface of module CS7, connector X01.
The parameters are summarized in the parameter list.
The STRUC G diagrams, supplied with the documentation are exclusively binding.
4.4.1
FP-IO
7KLVIXQFWLRQSDFNDJHLQFOXGHV
♦
Signal inputs (SUL, IT41, SS - L2DP)
♦
Basic/standby changeover for command and setpoint sources
♦
Enabling the sources for the OFF1 command
♦
Assignment of the sources for control words 1 and 2
♦
Assignment of the checkback signals
(transformer, circuit-breaker, motor and cooling unit)
♦
Error- and alarm messages from the FP IO