SIMOVERT MV Commissioning Instructions
23
&RQQHFWLQJXSWKHGLJLWDOVSHHGDFWXDOYDOXHHQFRGHU
The tachometer signals should be connected at terminal strip -X100.
External equipment
Internal equipment
(plant/system side)
System ground
55A
X100
55B
55C
X100
55D
56A
X100
56B
57C
X100
57D
57A
X100
57B
56C
X100
56D
58C
X100
58D
58A
X100
58B
Track 1 neg.
Track 1
Track 2 neg.
Track N neg.
Track 2
Track N
M24V
P24V
A131 (SU10) interface module 1:1 to
-A200-D05- (IT41)
SU10 :
Voltage range ±60 V
Current range, max. 0.5 A
IT41 :
Input voltage range:
Differential voltage,
−
30 V to +30 V
0 signal
−
30 V to +4 V
1 8 V to +30 V
Max. pulse frequency, 1 MHz
Phase difference of the track signals
Min. 200 ns
from SITOP
G130 power supply
Cable
Housing ground
P 24 V
M 24 V