Siemens AG 6SE8004-0BH76
SIMOVERT MV Commissioning Instructions
91
5.2.3
Commands to the drive converter (binary value processing)
%
.
.
.
%
Keys B1 to B4 can always be selected, with the exception when system processing
has been selected (SYSTEM).
The LED on the four binary keys indicates whether the appropriate binary value is
at "0" (LED dark) or at "1" (LED bright). The status is inverted by pressing the key.
The LED flashes each time the key is pressed, until SIMADYN D acknowledges
the change.
If the binary values are not configured on the SIMADYN D side, then the
LEDs of keys B1to B4 remain dark (this means that the keys have no effect).
%,1
and
or
Start of the binary value menu. Binary values B5 to B32 are processed.
The binary values cannot be saved in the EPROM of SIMADYN D. If this is
required, the binary values must be configured as process data in SIMADYN D.
The actual function is exited using:
6<67(0
6<6
06*
06*
9$/
$VVLJQLQJWKHELQDU\YDOXHVIRU6,029(5709GULYHFRQYHUWHUV
The software supports the command keys B3 and B4 and the binary values B5 to
B9.
♦
&RPPDQGNH\%
The command key B3 [LT] initiates the lamp test for the signal lamps in the front
panel of the drive converter.
♦
&RPPDQGNH\%
The command key B4 [Acknowledge] is used to acknowledge drive converter
faults. The acknowledge signal is generated at each edge change.
♦
%LQDU\YDOXH
This manually triggers the trace blocks. The trace is stopped using this command.
Actual values, saved in the ring buffer, can be read-out. The trace recording is also
stopped by a class 1 error, class 2 error, or a threshold comparison.
For the threshold comparison, a selected actual value is compared with a freely
selectable threshold.
The trigger conditions > = < are possible.
♦
%LQDU\YDOXH
Trace record enable. The trace record is enabled using this command. The actual
values are cyclically written into the ring buffer.
♦
%LQDU\YDOXH
Trace output. The values saved in the ring buffer are output using this command. If
the command is repeated, the output is repeated. This command does not delete
the ring buffer.
♦
%LQDU\YDOXH
This deletes the ring buffer trace. This command deletes the values saved in the
ring buffer.
♦
%LQDU\YDOXH
When the drive converter is in the OFF condition, the fan or the cooling unit can be
powered-up with binary value 9 from the OP2 operator control device.