Mounting, wiring, connecting, system interfaces, configuration guidelines
12.2 Wiring, connecting
SIMOCODE pro
212
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Terminal assignment of the multifunction module
Table 12- 13 Assignment of the removable terminals, multifunction module
Terminal Assignment
Upper terminals
IN1
Digital input IN1
IN2
Digital input IN2
IN3
Digital input IN3
SPE
1)
System shielding
IN-
Ground for IN1 to IN4
IN4
Digital input IN4
C1
Terminal 1, 3UL23 residual current
transformer
C2
Terminal 2, 3UL23 residual current
transformer
Lower terminals
T1
Input T1, temperature sensor
T2
Input T2, temperature sensor
T3
Input T3, temperature sensor
13
Common potential for relay outputs 1
and 2
14
Relay output OUT1
24
Relay output OUT2
1)
Note
Connect SIMOCODE pro via terminal SPE with the maximum possible cross-section and
with as short a cable as possible to the functional ground of the control cabinet, e.g. to the
grounded mounting plate of the control cabinet.