Commissioning, service, troubleshooting
13.4 Troubleshooting
SIMOCODE pro
298
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Event
(alphabetical)
Description
Troubleshooting
Acknowledgment /
fault rectification
Contactor
control
Error
No.
1)
Status -
cooling down
period active
The motor feeder has been
switched off due to overload.
The motor can only be
switched on again after
the cooling down period
has expired.
Status - DM-
F enabling
circuit
Shows the status of the enabling
circuit:
•
closed or
•
tripped
Status -
emergency
start
executed
The thermal memory has been
cleared with the function
"Emergency start".
The motor can be
switched on again
immediately after an
overload trip.
Status - test
position
(TPF)
The motor feeder is in the test
position (TPF). The main circuit
has been interrupted and the
feeder can be "cold started".
17
Stop time > The configured limit value for
motor stop time monitoring has
been exceeded.
Please adopt the
maintenance measures
intended for the feeder. If
possible, switch on the
feeder.
Fault - bus
Bus communication has been or
is being interrupted.
Check the bus connection
(plugs, cables, etc.).
Reset, auto-reset Tripped
5
Fault -
PLC/PCS
The PLC that controls the feeder
was or is in STOP mode.
Check the operating state
of the PLC.
Reset, auto-reset Tripped
6
Fault
antivalence
The limit switches are not
reporting any antivalent signals.
•
Limit switch open
circuit
•
Please check the
positioner application
and the limit switches.
Counter command
"OPEN/CLOSED"
Tripped
16
Fault -
EM open
circuit
A short circuit has occurred in the
wiring to the 3UL23 residual
current transformer.
Check the wiring to the
3UL23 residual current
transformer
Reset
Tripped
38
Fault -
EM short-
circuit
A short-circuit has occurred in
the wiring to the 3UL23 residual
current transformer.
Check the wiring to the
3UL23 residual current
transformer
Reset
39
Fault end
position
Positioner/solenoid valve has left
the end position without a
command being issued. The
motor feeder has been turned off.
Acknowledge the fault by
releasing with the counter
command
"OPEN/CLOSED".
Reset; counter
command
Tripped
15
Fault -
temporary
components
(e.g. memory
module)
One of the following components
is defective:
•
Memory module
•
PC cable.
Replace the defective
components. See Chapter
components (Page 279).
Clear the fault;
reset
Tripped
2
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...