Commissioning, service, troubleshooting
13.3 Service
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
277
13.3.2
Backing up and saving parameters
Always save the parameters in the memory module or in a SIMOCODE ES file. This
particularly applies if you replace a basic unit, or if you wish to transfer data from one basic
unit to another.
Saving parameters from the basic unit into the memory module
Note
This function will not be available if the TEST / RESET button has been disabled.
Proceed as follows:
Table 13- 15 Saving the parameters into the memory module
Step
Description
1.
Plug the memory module into the system interface. The "Device" LED lights up yellow for
approx. 10 seconds. During this time, press the "TEST / RESET" button for approx.
3 seconds. The parameters will be saved in the memory module. After successful data
transfer, the "Device" LED flickers yellow for approx. 3 seconds.
2.
If necessary, unplug the memory module from the system interface.
Saving parameters from the memory module into the basic unit
Note
This function will not be available if the TEST / RESET button has been disabled.
Proceed as follows:
Table 13- 16 Saving parameters from the memory module into the basic unit
Step
Description
1.
Plug the memory module into the system interface. The "Device" LED lights up yellow for
approx. 10 seconds. During this time, briefly press the "TEST / RESET" button. The
parameters will be transferred to the basic unit. After successful data transfer, the "Device"
LED flashes yellow for approx. 3 seconds.
2.
If necessary, unplug the memory module from the system interface.
Note
If the memory module is plugged in, the parameters will be transferred from the memory
module to the basic unit when the supply voltage is switched on.
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...