Commissioning, service, troubleshooting
13.4 Troubleshooting
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
301
Event
(alphabetical)
Description
Troubleshooting
Acknowledgment /
fault rectification
Contactor
control
Error
No.
1)
Warning
level U<
undershot
The voltage in the motor feeder
has undershot the warning level.
Possible causes:
•
Undervoltage in the network
•
Fuse has tripped.
Check the motor feeder.
Warning level
0/4 - 20 mA <
undershot
The measured value at the
analog input has undershot the
warning level.
Check the measuring
station.
Warning level
0/4 - 20 mA >
overshot
The measured value at the
analog input has overshot the
warning level.
Check the measuring
station.
Permissible
number of
starts
exceeded
The permissible number of starts
in the monitoring timeframe has
already been exceeded. The next
start should not be carried out
until the interlocking time has
expired.
Reset
Tripped
52
1) See also "Error number" in Chapter "Data record 72 - Error buffer" in the
manual SIMOCODE pro - Communication
https://support.industry.siemens.com/cs/ww/en/view/109743960
).
Note
2) Parameter block
On devices in the as-delivered condition or after the factory settings have been restored, the
parameter block is not active!
3) SIMOCODE pro fail-safe digital modules
https://support.automation.siemens.com/WW/view/en/50564852
4) Parameterizing SIMOCODE pro
https://support.industry.siemens.com/cs/ww/en/view/109743958
5) SIMOCODE pro - Communication
https://support.industry.siemens.com/cs/ww/en/view/109743960
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...