3UF50 compatibility mode
11.3 Diagram of diagnostics data
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
183
Byte.
Bit
Setup 3UF50 -
Device-specific diagnostics
according to DP standard
SIMOCODE DP
Byte.
Bit
Setup 3UF50 -
Device-specific diagnostics
according to DPV1 SIMOCODE DP
Equivalent in SIMOCODE pro V
12.1 Trip: OPO
15.1 Trip: OPO
Fault - Operational Protection
Off (OPO)
12.2 Trip: UVO
15.2 Trip: UVO
Fault - power failure (UVO)
12.3 Trip: Ext. fault 1
15.3 Trip: Ext. fault 1
Fault - ext. fault 1
12.4 Trip: Ext. fault 2
15.4 Trip: Ext. fault 2
Fault - ext. fault 2
12.5 Trip: TPF fault
15.5 Trip: TPF fault
Fault - Test Position Feedback
(TPF)
12.6 Trip: Runtime ON
15.6 Trip: Runtime ON
Fault - execution ON command
12.7 Trip: Runtime OFF
15.7 Trip: Runtime OFF
Fault - execution STOP
command
13.0 Trip: Parameter fault 0
16.0 Trip: Parameter fault 0
Fault - parameterization
13.1 Trip: Parameter fault 1
16.1 Trip: Parameter fault 1
—
13.2 Trip: Parameter fault 2
16.2 Trip: Parameter fault 2
—
13.3 Trip: Parameter fault 3
16.3 Trip: Parameter fault 3
—
13.4 Trip: Parameter fault 4
16.4 Trip: Parameter fault 4
Fault - configuration error
13.5 Trip: Parameter fault 5
16.5 Trip: Parameter fault 5
13.6 Trip: Parameter fault 6
16.6 Trip: Parameter fault 6
13.7 Trip: Parameter fault 7
16.7 Trip: Parameter fault 7
Fault - hardware fault basic unit
14 -
15
Number of overload trips
Number of overload trips
16 -
17
I of the overload trip [% / IE)]
Last trip current
18 -
19
Operating hours [10 h]
Motor operating hours
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...