Technical data
15.4 Technical data of the current measuring modules and the current / voltage measuring modules
SIMOCODE pro
344
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Technical data of the current measuring modules or the 1st generation current / voltage measuring modules
Connection for voltage measurement
•
Tightening torque
TORQUE: 7 lb.in - 10.3 lb.in
0.8 Nm to 1.2 Nm
•
Connection cross sections
- Solid
1 x 0.5 mm
2
- 4 mm
2
/ 1 x AWG 20 to 12
2 x 0.5 mm
2
- 2.5 mm
2
/ 2 x AWG 20 to 14
- Finely stranded with end sleeve
1 x 0.5 mm
2
- 2.5 mm
2
/ 1 x AWG 20 to 14
2 x 0.5 mm
2
- 1.5 mm
2
/ 2 x AWG 20 to 16
1) for 3UF7103 or 3UF7104 to 1000 V
2) for 3UF7103 or 3UF7104 to 8 kV
3) You will find more information at SIMOCODE pro (
https://www.siemens.com/simocode
) and in Chapter Short-circuit
measuring module (Page 364)
4) Screw connection is possible with an appropriate 3RT19 box terminal.
5) When connecting cable lugs complying with DIN 46235 to cables with a cross section larger than 95 mm
2
, the
3RT19 56-4EA1 terminal cover is required to maintain phase separation.
6) When connecting cable lugs complying with DIN 46234 to cables with a cross section larger than 240 mm
2
and when
connecting cable lugs complying with DIN 46235 to cables with a cross section larger than 185 mm
2
, the 3RT19 56-4EA1
terminal cover is required to maintain phase separation.
7) Valid for float values
8) A current range of 0.4 - 8 A is necessary for the 3UF7110-1AA01-0 version
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...