![Siemens SIMOCODE pro C System Manual Download Page 226](http://html.mh-extra.com/html/siemens/simocode-pro-c/simocode-pro-c_system-manual_1265400226.webp)
Mounting, wiring, connecting, system interfaces, configuration guidelines
12.2 Wiring, connecting
SIMOCODE pro
226
System Manual, 05/2019, A5E40507475002A/RS-AD/004
12.2.3
Wiring of current measuring modules
Selection
Select the appropriate current measuring module according to the motor current:
●
Through-hole connection up to 200 A: The cables of the three phases are passed through
the feed-through openings.
●
Bus connection system from 20 A to 630 A, also for direct connection to Siemens
contactors.
The following table shows the various current measuring modules:
Table 12- 20 Current measuring modules
Current measuring module
Version
3UF7100-1AA00-0; 0.3 to 3 A
Ø feed-through openings: 7.5 mm
Through-hole connection
3UF7101-1AA00-0; 2.4 to 25 A
Ø feed-through openings: 7.5 mm
3UF7102-1AA00-0; 10 - 100 A
Ø feed-through openings: 14 mm
3UF7103-1AA00-0; 20 to- 200 A
Ø feed-through openings: 25 mm
3UF7103-1BA00-0; 20 to 200 A
Conductor cross section: 16 to 95 mm²,
AWG 5 to 3/0
Bus connection system
3UF7104-1BA00-0; 63 to 630 A
Conductor cross section:
50 to 240 mm², AWG 1/0 to 500 kcmil
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...