Description of system components
8.3 Operator panel with display
SIMOCODE pro
92
System Manual, 05/2019, A5E40507475002A/RS-AD/004
8.3.2
Operator controls and display elements of the operator panel with display
Displays of the operator panel with display
The display shows current measured values, operating data and diagnostics data as well as
the status information of the motor feeder in plain text or with the aid of symbols.
Figure 8-10 Display elements of the operator panel with display
1
Shows the current setting Is / rated motor current in A. For motors with two speeds, the
relevant current setting Is1 or Is2 is always displayed depending on whether the current
speed is slow or fast, e.g. 8 A. For motors with two speeds, the left-hand softkey can be
used when the motor is stopped to alternate between the display of the two current settings.
When running, the current setting for the active motor speed is always displayed.
2
Shows the set class time of the overload protection system, e.g.:10 = class 10
(class = trip class)
3
Indicates that temperature monitoring is active, e.g. the motor temperature is being
monitored by thermistors or analog temperature sensors (Pt100, Pt1000, KTY, NTC).
(T= temperature monitoring active.)
4
The main display enables customized depiction of different measured values when running.
This is the standard display at the topmost menu level. Predefined profiles in the display
settings can be selected for this purpose. By pressing the "Menu" softkey on the right, you
can navigate through the submenus of the main display (see Chapter Read and adapt main
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...