Commissioning, service, troubleshooting
13.2 Commissioning
SIMOCODE pro
270
System Manual, 05/2019, A5E40507475002A/RS-AD/004
13.2.4
Commissioning with EtherNet/IP
13.2.4.1
EtherNet/IP commissioning steps
Please observe the information in Chapter General information about commissioning and
service (Page 255).
To commission SIMOCODE pro, proceed as follows:
Table 13- 12 Commissioning the basic unit
Step Description
1
Switch on the power supply. In a fault-free state, the following LEDS should light up green:
•
"Device" (lights up)
•
"PORT 1 / PORT 2" when the Ethernet cable is connected (lighted or flashing).
Continue with step 2.
Otherwise, carry out diagnostics according to the LED display. For more information, see Chapter Diagnostics via
LED display on the basic unit and on the operator panel with EtherNet/IP (Page 274). Try to rectify the fault.
2
If you want to make SIMOCODE pro available to EtherNet/IP, you must set the IP parameters and the device
name. For more information, see Chapter Setting IP parameters and EIP device name (Page 271).
3
Parameterize SIMOCODE pro or check the existing parameterization, e.g. with a PC on which SIMOCODE ES
software is installed. For this, connect the PC / PG to the system interface with the PC cable (see the figure below).
4
Start SIMOCODE ES.
Figure 13-5 Connecting a PC to the basic unit
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...