Description of system components
8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000)
SIMOCODE pro
142
System Manual, 05/2019, A5E40507475002A/RS-AD/004
8.6
Decoupling module (DCM) for 1st generation current/voltage
measuring modules (e.g. 3UF711.1AA000)
Function of the decoupling module
When measuring voltage and power with SIMOCODE pro in ungrounded networks, each
current / voltage measuring module must have a decoupling module connected upstream in
series at the system interface. Where voltage or power is measured with SIMOCODE pro in
systems with additional insulation measurement or insulation monitoring, a decoupling
module must be connected between the basic unit and each current / voltage measuring
module. If using the 3UF710 current measuring module in these networks, it is imperative
that an additional decoupling module is not used.
Figure 8-32 Decoupling module, SIMOCODE pro V device series
Note
Connectable expansion modules
When using a decoupling module, note that the type and number of expansion modules that
can be connected to a basic unit are limited! See Chapter Configuration information for
SIMOCODE pro V when using an older basic unit (Page 155).
Note
Using the decoupling module
Do not use the decoupling module with the 2nd generation current / voltage measuring
modules.
In the event that a 1st generation current / voltage measuring module is replaced by a
2nd generation current / voltage measuring module, remove the decoupling module.
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...