Mounting, wiring, connecting, system interfaces, configuration guidelines
12.1 Mounting
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
191
12.1.5
Mounting the current / voltage measuring modules
You can attach these system components as follows:
●
Current / voltage measuring modules up to 115 A: Standard mounting rail mounting or
screw attachment with mounting lugs (article number: 3RV2928-0B) and screws for
mounting on a level surface. These mounting lugs are suitable only for current / voltage
measuring modules (and current measuring modules)! For current / voltage measuring
modules up to 25 A you will require an additional spacer, 25 mm in length.
●
Current / voltage measuring modules up to 200 A: Standard mounting rail or screw
attachment.
●
Current / voltage measuring modules up to 630 A: Screw mounting
Note
Current / voltage measuring modules with a current setting of up to 115 A can be connected
to the basic unit mechanically and installed as a unit (behind one another).
Larger current / voltage measuring modules can only be mounted separately.
Figure 12-5 Mounting the current / voltage measuring modules UM+ with through-hole technology
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...