Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
103
Technical data
Number of simultaneously controllable inputs
Horizontal installation
Up to 40 °C
Up to 60 °C
24
24 (with 24 V)
18 (with 28.8 V)
Vertical installation
Up to 40 °C
24
Electrical isolation
Between channels and backplane bus
Yes
Between channels in groups of
12
Maximum potential difference between different
circuits
75 V DC
60 V AC
Insulation test voltage
500V DC / 350V AC for 1 min
or 600V DC for 1s
Current consumption
From backplane bus
100 mA, maximum
From load voltage 1L+, 2L+ (no sensors)
450 mA, maximum
Power loss of the module
10 W, typical
Status, Interrupts, Diagnostics
Status display
Green LED per channel
Interrupts
Diagnostic interrupt
Programmable
Diagnostics functions
Programmable
Group fault display
Red LED (SF)
Fail-safe mode display
Green LED (SAFE)
Diagnostic information can be read out
Possible
Sensor Supply Outputs
Number of outputs
4
Electrical isolation between channels and
backplane bus
Yes
In groups of
2
Output voltage
Loaded
Minimum L+ (-1.5 V)
Output current
Rated value
400 mA
Approved range
0 to 400 mA
Additional (redundant) infeed
Permissible
Short-circuit protection
Yes, electronic
Sensor selection data
Input voltage
Rated value
24 V DC
For "1" signal
11 to 30 V
For "0" signal
- 30 to 5 V