Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
264
Installation and Operating Manual, 01/2010, A5E00085586-10
Technical data
Electrical isolation
Between channels 0/1/2 and 3/4/5, backplane
bus, load voltage L+/sensor supply Vs0...5,
shield
Yes
Between channels 3/4/5 and 0/1/2, backplane
bus, load voltage L+/sensor supply Vs0...5,
shield
Yes
Between backplane bus and channels 0/1/2,
channels 3/4/5, load voltage L+/sensor supply
Vs0...5, shield
Yes
Between load voltage L+/sensor supply Vs0...5
and channels 0/1/2, channels 3/4/5, backplane
bus, shield
Yes
Between shield and channels 0/1/2, channels
3/4/5, backplane bus, load voltage L+/sensor
supply Vs0...5
Yes
Between the channels of a potential group
No
Permitted potential difference
Between the potential groups
75 V DC, 60 V AC
Between the channels (0/1/2 or 3/4/5) of a
potential group
75 V DC, 60 V AC
Insulation test voltage
370 V AC for 1 min.
Current consumption
From backplane bus
90 mA, maximum
From supply voltage L+ (without load)
Typ. 150 mA
Common-mode voltage (CMV)
Permitted common mode voltage between the
inputs (U
CM
)
75 V DC, 60 V AC
Permitted common mode voltage between the
inputs and M
75 V DC, 60 V AC
Power loss of the module
4.5 W, typical
Analog value generation
Measuring principle
DELTA-SIGMA
Integration/conversion time
Assignable
Yes
Integration time
At 50 Hz
At 60 Hz
20 ms
16.67 ms
Response time per channel pair
At 50 Hz
At 60 Hz
25 ms
22 ms
Basic response time
50 ms
Resolution, including overrange
15 bits + sign
Smoothing of measured values (per channel)
Yes, assignable