Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
261
Diagnostic message
Possible causes of the problem
Corrective measures
Measuring range fallen below
Use suitable sensor,
check wiring (sensor polarity
reversed)
Check sensor setting
Measuring range exceeded
Use a suitable sensor; sensor polarity
reversed
Overflow or underflow of the
measured value (see "Wire break
and underflow") in Chapter "Analog
value representation (Page 222)")
Current through sensor too high at
startup
—
Check the communication connection
Error in communication between the CPU
and the module, for example, due to
defective PROFIBUS connection or
electromagnetic interference in excess of
limits
Eliminate the interference
Timeout of safety message frame
monitoring
Check the monitoring time parameters
CRC signature error, for example, due to
electromagnetic interference in excess of
limits or standard program accessing F-
SM.
Eliminate the interference
F-CPU has gone into STOP mode
Read out the diagnostic buffer of the
F-CPU
Communication error
Inconsistent parameter assignment in
HW Config
and F-program
Recompile the project and download the
S7 program again.
HART: Primary variable outside the
limits
Assigned primary variable is outside
the limits
Incorrect parameters in the HART
field device
HART field device has simulation,
and simulation setting is "Primary
variable outside the limits"
HART: Non-primary variable
outside the limits
Assigned non-primary variable is
outside the limits
Incorrect parameters in the HART
field device
HART field device has simulation,
and simulation setting is "Non-primary
variable outside the limits"
HART: Analog output current
saturated
Incorrect parameters in the HART
field device
HART field device has simulation,
and simulation is set to a measured
value that is too high
Assigned primary variable is outside
the limits
Check the parameter assignment of
the HART field device
Correct/deactivate simulation
Check whether the correct sensor is
connected
End the measuring circuit test