Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
101
Diagnostic message
Possible causes of the problem
Corrective measures
Overload due to diagnostics request
(SFCs)
Reduce the number of
diagnostics requests
Electromagnetic interference has
exceeded limits
Eliminate the interference
Time monitoring activated
(watchdog)
Defective module
Replace the module
Electromagnetic interference has
exceeded limits
Eliminate the interference and
cycle the power supply OFF/ON
EPROM error
RAM error
Defective module
Replace the module
Electromagnetic interference has
exceeded limits
Eliminate the interference
Defective module
Replace the module
Processor failure
Switching rate exceeded
Reduce switching rate
Internal error in read
circuit/test circuit
Defective module
Replace the module
CRC signature error
CRC signature error during
communication between the CPU
and the module has occurred, for
example, due to electromagnetic
interference in excess, faults during
sign-of-life monitoring error or
standard program accesses F-SM.
Eliminate the interference
Assigned monitoring time exceeded Check the monitoring time
parameters
Timeout of safety message
frame monitoring
Startup of the fail-safe signal module —
Message frame error
Sign-of-life and/or CRC signature
entered in the data message frame
Check the sign-of-life and CRC
signature entries in the data
message frame for "0" value