Analog modules
9.2 SM 336; AI 6 x 13 Bit
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
191
Wiring schemes
Three wiring schemes are available for each application, depending on the type of
measurement.
Table 9- 4
Wiring scheme of SM 336; AI 6 x 13 Bit
Wiring scheme
Measurement type
Range
Channels
Abbreviation in
HW Config
A
Current measurement with
2-wire transducer
4 to 20 mA
0 to 5
2DMU
B
Current measurement with
4-wire transducer
4 to 20 mA
0 to 20 mA*
0 to 5
4DMU
C
Voltage measurement*
0 V to 10 V
0 to 3
V
* Current measurement 0 to 20 mA and voltage measurement are only supported in standard mode.
Note
In the wiring schemes below, the connections to the reference point of the measuring circuit
M
ANA
are represented by a dashed line. This means these connections are recommended
options (see chapter "Properties, front view, wiring diagram and block diagram (Page 184)").
A dashed connection between two or four sensors indicates that these sensors measure the
same process variable.
9.2.4
Application 1 : Standard Mode
Introduction
Below are the wiring schemes and the parameter assignment of SM 336; AI 6 x 13Bit for
●
Application 1: Standard mode
Diagnostic messages, possible causes of the problem and their corrective measures are
found in tables
Diagnostic messages of SM 336; AI 6 x 13Bit and Diagnostic messages and
associated corrective measures for SM 336; AI 6 x 13Bit in chapter "Diagnostic Messages