Digital modules
8.7 SM 326; F-DO 10 x DC 24V/2A PP (6ES7326-2BF10-0AB0)
Fail-safe signal modules
168
Installation and Operating Manual, 01/2010, A5E00085586-10
Connecting two actuators to one digital output
The fail-safe digital output is capable of switching two actuators. The following conditions
have to be met:
●
Wire L+ and M of the actuators to 2L+ and 2M of the module (same reference potential
required).
The actuators can be wired to any one of the 10 digital outputs. The figure below shows an
example of an output wiring. This circuit is compliant with SIL 3/Cat. 4/PLe.
/
0
/
0
'2
60
)'2['&9$33
Figure 8-58 Wiring scheme 2 actuators at digital output of SM 326; F-DO 10 x DC 24V/2A PP
WARNING
It is no longer possible to shut down an actuator if a cross circuit has developed between
2L+ and DO. To prevent cross circuits between 2L+ and DO, you must route the cables
used to connect the actuators in a cross-circuit-proof manner (for example, as separate,
sheathed cables or in separate cable ducts).
Assignable parameters for application 5
Table 8- 23 Parameters for application 5 of SM 326; F-DO 10 x DC 24V/2A PP
Parameters
Range of values
Type
Effective
range
"Parameters" tab
Mode of operation
Safety mode
Static
Module
F_Monitoring_Time (ms)
10 ms to 10000 ms
Static
Module
Diagnostic interrupt
Activated/deactivated
Static
Module
Fail-safe value
Switch to fail-safe value "0"
Keep last valid value
Static
Module
Maximum test period
100 / 1000 s
Static
Module
Load voltage failure diagnostics
Activated/deactivated
Static
Channel
group
Activated
Activated
Static
Channel
Diagnostics: Wire break
Activated/deactivated
Static
Channel
Activated light test
Activated/deactivated
Static
Channel
Max. time for light test (ms)
0.6 ms to 5 ms
Static
Channel
Max. read-back time for dark test
(ms)
0.6 ms to 400 ms
Static
Channel
Redundant switched
Deactivated
Static
Channel