Analog modules
9.2 SM 336; AI 6 x 13 Bit
Fail-safe signal modules
206
Installation and Operating Manual, 01/2010, A5E00085586-10
WARNING
To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor.
Assignable parameters for application 4
Table 9- 8
Parameters for application 4 of SM 336; AI 6 x 13Bit
Parameters
Range of values in safety mode
Type
Effective range
"Inputs 1" tab
Enable diagnostic
interrupt
Activated/deactivated
Static
Module
Interference frequency 50 Hz/60 Hz
Static
Module
Group diagnostics
Activated/deactivated
Static
Channel
Wire-break check (only
for 4 to 20 mA)
Activated/deactivated
Static
Channel
Measurement type
Deactivated
4DMU
2DMU
Static
Channel
Measuring range
4 to 20 mA
Static
Channel
"Inputs 2" tab
Safety mode
According to SIL 2
1 sensor
Static
Module
Monitoring time
10 ms to 10000 ms
Static
Module
"Redundancy" tab
Redundancy
2 modules
static
module
Redundant module
Selection of an existing additional
module of the same type
static
Redundant module
pair
9.2.8
Application 5: Safety mode SIL3/Cat.4/PLe
Introduction
Below are the wiring schemes and the parameter assignment of SM 336; AI 6 x 13Bit for
●
Application 5: Safety mode SIL3/Cat.4/PLe.
Diagnostic messages, possible causes of the problem and their corrective measures are
found in tables
Diagnostic messages of SM 336; AI 6 x 13Bit and Diagnostic messages and
associated corrective measures for SM 336; AI 6 x 13Bit in chapter "Diagnostic Messages