Digital modules
8.7 SM 326; F-DO 10 x DC 24V/2A PP (6ES7326-2BF10-0AB0)
Fail-safe signal modules
176
Installation and Operating Manual, 01/2010, A5E00085586-10
Diagnostic message Error detection Possible causes of the problem
Corrective measures
Overload due to diagnostics
request (SFCs)
Reduce the number of
diagnostics requests
Electromagnetic interference has
exceeded limits
Eliminate the
interference
Time monitoring
activated
(watchdog)
general
Defective module
Replace the module
Error in communication between
the CPU and the module, for
example, due to defective
PROFIBUS connection or
electromagnetic interference in
excess of limits.
Check the PROFIBUS
connection
Eliminate the
interference
Timeout of data frame monitoring
Check the monitoring
time parameters
CRC signature error, for example,
due to electromagnetic interference
in excess of limits.
Eliminate the
interference
Communication
error
general
CPU is in STOP
Read the diagnostics
buffer
Electromagnetic interference has
exceeded limits
Eliminate the
interference and cycle
power supply OFF/ON
EPROM error
RAM error
general
Defective module
Replace the module
Internal error in
read / test
sequence
General
Defective module
Replace the module
Electromagnetic interference has
exceeded limits
Eliminate the faults, and
then remove and insert
the module
Defective module
Replace the module
Processor failure
general
Switching rate exceeded
Reduce switching rate
Parameter
assignment error
(with specification of
a consecutive
number)
general
Error in dynamic parameter
reassignment
Check the parameter
assignment in the user
program. Contact
SIMATIC Customer
Support if necessary
No external
auxiliary voltage
general
Supply voltage 1L+ of module
missing
Connect 1L+
External load
voltage missing
general
Supply voltage 1L+ of module
missing
Feed in voltage supply
Defective main
switch
general
Defective module
Replace the module
Defective output
driver
general
Defective module
Replace the module
Output overload
Eliminate the cause of
overload
Overtemperature at
output driver
general
Internal fault at output driver
Replace the module