Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
89
Wiring scheme for application 4 with single-channel connection of two redundant sensors
Two redundant sensors are each connected via one channel to the two analog modules for
each process signal (1oo1 evaluation). The sensors can also be connected to an external
sensor supply.
/
0
',
9V
/
0
',
9V
60
',['&9
60
',['&9
$FTXLVLWLRQRIWKHVDPH
SURFHVVYDULDEOHXVLQJ
PHFKDQLFDOO\VHSDUDWHG
VHQVRUV
Figure 8-12 Wiring scheme of the SM 326; DI 24 x DC 24V for application 4 – two redundant sensors
single-channel connection
WARNING
To achieve SIL2/Cat.3/PLd using this wiring, you must use a suitably qualified sensor.
Assignable parameters for application 4
Table 8- 5
Parameters for application 4 of SM 326; DI 24 x DC 24V
Parameters
Range of values in safety mode
Type
Effective range
"Parameters" tab
Mode of operation
Safety mode
Static
Module
F parameter:
F monitoring time
10 ms to 10000 ms
Static
Module
Module parameters:
Diagnostic interrupt
activated/deactivated
Static
Module
Module parameters for a power supply group:
Internal sensor supply
of the module
Activated/deactivated
Static
Power supply group
Short-circuit test
activated/deactivated * (only if "Sensor
Supply via Module" is activated)
static
Power supply group
For single channels or channel pairs:
activated
activated/deactivated
static
channel
Evaluation of the
sensors
1oo1 evaluation
static
channel
"Redundancy" tab
Redundancy
2 modules
static
module