background image

AT3-II S

CEE Adapter 16 (20) A 
for Testing Protective Conductor Current in Operating Condition

3-349-337-03

5/7.14

Operating Instructions

1

Application

With the AT3-II S CEE adapter, devices which are equipped with 
a 16A/6h or 32A/6h 5-pin CEE plug can be quickly and efficiently 
connected to test instruments designed for testing portable 
devices in accordance with DIN VDE 0701-0702, or for testing in 
accordance with IEC 62353 (VDE 0751), and which are furnished 
with only an earthing contact outlet.
The following tests can be performed on devices with CEE plugs 
with the help of the AT3-II S adapter:

Testing of protective conductor continuity

Insulation resistance measurement

Measurement of Protective Conductor Current in measuring mode
– direct (direct method via test socket)
– differential (differential current measuring method)
– alternative (equivalent leakage current measurement method)

Attention

!

!

Application Restrictions

 

The AT3-II S CEE adapter may only be used for test 
purposes in combination with a test instrument. Other use 
of the adapter, in particular for continuous connection of 
3-phase current devices to 3-phase electrical systems, is 
not permissible under any circumstances!
In any case, maximum permissible conventional thermal 
current is 16 A AC per phase.

2

Safety Features and Precautions

The AT3-II S CEE-Adapter is manufactured and tested in 
accordance with safety regulations IEC 61010-1 / EN 61010-1 / 
VDE 0411-1. If used for its intended purpose, the safety of the 
user and of the device is assured. 
Carefully read the operating instructions before use, in particular 
the operating instructions included with the test instrument with 
which you intend to use the adapter. Follow all instructions 
contained therein.
The adapter may only be used for testing devices with 5-pin CEE 
plugs and current consumption of no greater than 3 x 20 A (AC-1).

The AT3-II S CEE adapter may not be used:

With open housing

If it demonstrates visible damage

If the CEE outlet or the connector cable is damaged

After excessive stress, i.e. if the load capacities specified in 
the technical data have been exceeded

After long periods of storage under unfavorable conditions 
(e.g. humidity, dust or extreme temperature)

Meanings of Symbols on the Instrument

Warning concerning a point of danger 
(attention: observe documentation!)

CAT II 

Measuring category II device
Indicates EC conformity
Harmlessness with regard to interference emission and 
interference immunity in accordance with 
EN 61326:2000 / EN 61000-2 / EN 61000-4

The device may not be disposed of with the trash. 
Further information regarding the WEEE mark can be 
accessed on the Internet at www.gossenmetrawatt.com 
by entering the search term WEEE.

3

Connecting the AT3-II S

Before testing can be started, the AT3-II S must be connected to 
the test instrument and to mains power. Proceed as follows:

Ð

Connect the mains cable from the test instrument to the 
earthing contact outlet labelled “Appliance tester” on the 
AT3-II S.

Ð

Connect the earthing contact cable from the AT3-II S to the 
test/mains outlet at the test instrument. The connection at the 
AT3-II S is labelled “to appliance tester”.

Note!
Prerequisite for differential current measurement

For the measurement of protective conductor current 
with differential current method you require a test instru-
ment which is equipped with voltage inputs.

Ð

Insert the 4 mm plugs on the cable from the AT3-II S, which is 
labelled “tester Bu. 2 & 3”, into sockets N (2) and L (3) at the 
test instrument.

Ð

Plug the CEE connector cable from the AT3-II S into a suitable 
16A/6h CEE outlet within your electrical installation. The 
connection at the AT3-II S is labelled “Mains, 3~ 400 V, 16 A 
50...60 Hz”. As of this point in time, the AT3-II S and the test 
instrument are supplied with electrical power.

Ð

Finally, connect the device under test to the CEE outlet at the 
AT3-II S. The outlet or coupling is labelled “Test-socket 
appliance”.

Testing can now be started (see section 4).

4

Testing with the AT3-II S

You can now execute all tests on devices with CEE plugs which 
are otherwise possible with the test instrument, and which are 
supported by the AT3-II S adapter, just as you would for devices 
with earthing contact plugs. Proceed as described in the operat-
ing instructions for the test instrument to this end.

The following characteristics of the AT3-II S adapter must be 
taken into consideration when performing tests with the test 
instrument:

Testing Protective Conductor Resistance

When testing protective conductor resistance, measured 
protective conductor resistance is increased by the amount 
caused by the protective conductor system of the AT3-II S CEE 
adapter itself. In case of doubt, i.e. if measurement results are 
close to the permissible limit value, measure the adapter’s 
protective conductor resistance at the PE terminal of its CEE 
outlet, and subtract the results from the measured value obtained 
for the DUT-adapter system.

Insulation Test

During insulation testing, the three phase terminals (L1, L2 and 
L3) and the neutral terminal (N) at the DUT are short-circuited, and 
testing is then executed.

!

Reviews: