7-19
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Table 7-8
Analog Input Module 464–8MF11, 2
PT 100 (Unipolar)
Analog Input Module 464–8MF21, 2
PT 100 “No Linearization” (Unipolar)
Units
Resistance in
High Byte
Low Byte
Range
>4095
w
400.0
0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1
Overflow
4095
2049
399.90
200.098
0
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
0
0
0
0
0
0
Overrange
2048
200.0
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1024
100.0
0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
Nominal Range
1
0.098
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
Nominal Range
0
0.0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Table 7-9
Analog Input Module 464–8MF21, 2
PT 100 “with Linearization” (Bipolar), to DIN IEC 751
Units
Resistance
in
Tempera-
ture in
°
C
High Byte
Low Byte
Range
>1766
>400
>883
0 0 1 1 0 1 1 1 0 0 1 1 0 0 0 1
Overflow
1766
1702
883
851
0
0
0
0
1
1
1
1
0
0
1
1
1
0
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
0
1
1
Overrange*
1700
390.26
850
0 0 1 1 0 1 0 1 0 0 1 0 0 0 0 0
1400
345.13
700
0 0 1 0 1 0 1 1 1 1 0 0 0 0 0 0
1000
280.90
500
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
600
212.02
300
0 0 0 1 0 0 1 0 1 1 0 0 0 0 0 0
300
157.31
150
0 0 0 0 1 0 0 1 0 1 1 0 0 0 0 0
200
138.50
100
0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 0
Nominal Range
2
100.39
1
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0
0
100.00
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–40
92.16
–20
1 1 1 1 1 1 1 0 1 1 0 0 0 0 0 0
–80
84.27
–40
1 1 1 1 1 1 0 1 1 0 0 0 0 0 0 0
–200
60.25
–100
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 0
–202
–494
–101
–247
1
1
1
1
1
1
1
1
1
0
0
0
0
0
1
0
1
1
0
0
1
0
1
1
0
0
0
0
0
0
1
1
Overrange*
<–494
<–247
1 1 1 1 0 0 0 0 1 0 0 1 0 0 0 1
Overflow
*
In the overrange, the current slope of the characteristic curve is maintained when leaving the linearized nominal range.
Analog Value Processing