8.10 Analog Output Modules
Analog Output Module 2
"
10 V
(6ES5 470–8MA12)
pr93a049
Technical Specifications
Address ID for ET 200U
S
DP Siemens
S
DP Standard
2AQ or 021
2AQ or 097
Output range
(rated values)
"
10 V
Number of outputs
2
Galvanic isolation
yes (outputs to
grounding point and
between outputs)
Input resistance
w
3.3 k
Capacitive load incl. cable
capacitance
<100 nF
Connection method
two– or four–wire
connection
Digital representation of output
signal
11 bits + sign (1024
units = rated value)
Measured value representation two’s complement
(left–justified)
Conversion time
(0 to 100 %)
max. 0.15 ms
Permissible overload
25 %
Short–circuit protection
yes
Short–circuit current
"
30 mA
Permissible voltage difference
to ground and between outputs max. 75 V DC/
60 V AC
Basic error limits
(operational error limit at
25
_
C, referred to input ranges
of module)
"
0.3 %
Operational error limits
(0 to 60
_
C, referred to input
ranges of modue)
"
0.6 %