8-36
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Technical Specifications
Address identifier for ET 200U
DP Siemens
DP Standard
8DQ or 017
8DQ or 032
Outputs
8 relay outputs, contact
switching varistor
SIOV–S07–K275
Galvanic isolation
in groups of
yes
2 with signal status
display
Continuous current I
th
3 A
Relay type
Dold OW 5699
Switching capacity of the con-
tacts
resistive load
inductive load
max. 3 A at 250 V AC
1.5 A at 30 V DC
max. 0.5 AC
at 250 V AC
0.5 A at 30 V DC
Operating cycles of the con-
tacts according to VDE 0660,
part 200
AC–11
DC–11
1
10
6
0.5
10
6
Switching frequency
max. 10 Hz
Fault LED (red)
no input voltage
Length of cable
unshielded
max. 100 m (330 ft.)
Rated isolation voltage
(+9 V to L1)
isolation group
tested with
250 V AC
2
B
1500 V AC
Rated isolation voltage
(+9 V to )
isolation group
tested with
12 V AC
1
B
500 V AC
Rated isolation voltage
(between contacts)
isolation group
tested with
250 V AC
2
B
1500 V AC
Supply voltage L+
(for the relay)
rated value
ripple V
pp
permissible range
(ripple included)
value when t < 0.5 s
24 V DC
max. 3.6 V
20 to 30 V
35 V
Current consumption
from +9 V (CPU)
from L+
typ. 30 mA
typ. 70 mA
Power loss of the module
typ. 1.6 W
Weight
approx. 300 g (11 oz.)
Module Spectrum