5-19
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
You want to replace one module with a different module in a station that you
have already configured.
1. In the CONFIGURING screen, press <F4> (NEW STATION) to select the
number of the station that you want to change.
COM ET 200 displays the configuration of the selected station. The “1st
available address” input field shows the address that will be assigned to the
new module.
2. Overwrite the address ID of the old module with the address ID of the
new module.
3. Press <F6> (ENTER) to confirm the configuration.
The new module has a module start address that is not consecutive in the or-
der of the addresses of the stations that you configured previously. The start
address reflects a jump in addressing.
The address space that the old module took up is released and could be used
for a module with the same address ID. If you wanted to put a module in such
a slot, you would have to edit the “1st available address” field. However, this
is not recommended.
Modifying an Al-
ready Configured
Slave Station
ET 200U(DP Standard): Address Assignm.,Starting–Up, Diagnosing Faults Using COM ET 200