Configuring with Web Based Management
4.4 "System" menu
SCALANCE SC-600 Web Based Management (WBM)
Configuration Manual, 10/2021, C79000-G8976-C475-03
209
4.4.15.2
Link Change
Configuration of fault monitoring of status changes on connections
On this page, you configure whether or not an error message is triggered if there is a
status change on a network connection.
If connection monitoring is enabled, an error is signaled
•
when there should be a link on a port and this is missing.
•
or when there should not be a link on a port and a link is detected.
A fault causes the fault LED on the device to light up and, depending on the
configuration, can trigger a trap or an entry in the event log table.
Description
Table 1 has the following columns:
•
1st column
Shows that the settings are valid for all ports.
•
Setting
Select the setting from the drop-down list. You have the following setting options:
–
"-" (disabled)
–
Up
–
Down
–
No Change: The setting in table 2 remains unchanged.
•
Copy to Table
If you click the button, the setting is adopted for all ports of table 2.