Configuring with Web Based Management
4.4 "System" menu
SCALANCE SC-600 Web Based Management (WBM)
150
Configuration Manual, 10/2021, C79000-G8976-C475-03
–
FMP Status Change
The value of the received power or the power loss has exceeded or fallen below a
certain limit.
Note
You can only configure this event in devices that support FMP.
–
NTP (secure)
This event occurs when the device receives the system time from a secure NTP
server.
–
Configuration Change
This event occurs when the configuration of the device has changed.
–
Service Information
For certain events, entries are made in the log table even without configuration.
For these events, you can configure additional subsequent actions here (e-mail,
Trap, Syslog).
–
DHCP Server Log
DHCP events are saved in the logbook.
•
The device sends an e-mail. This is only possible if the SMTP server is set up and the
"SMTP Client" function is enabled.
•
Trap
The device sends an SNMP trap. This is only possible if "SNMPv1 Traps" is enabled
in "System > Configuration".
•
Log Table
The device writes an entry in the event log table, see "Information > Log Table".
•
Syslog
The device writes an entry to the system log server. This is only possible if the system
log server is set up and the "Syslog client" function is enabled.
•
Fault
Select for which events the device is to trigger a fault. The fault is signaled by the
fault LED lighting up.
•
Digital Out
Controls the digital output.
By default, the digital output is closed, which means the signaling contact is open.
The digital output is opened as soon as you enable at least one event for the digital
output under "Events > Configuration". It also is no longer automatically connected to
the fault LED. You connect the digital output with the fault LED under "Fault State
Change".