PREMASREG

® 

716x - Q 

LCD  

PREMASREG

® 

716x 

LCD  

D

  

Bedienungs- und Montageanleitung

Druck-Messumformer ⁄ -Schalter ⁄ -Wächter   
für Volumenstrom, Differenzdruck, Filterüberwachung und 
Flüssigkeits-Niveauerfassung, incl. Anschluss-Set

G

  

Operating Instructions, Mounting & Installation

Pressure measuring transducer ⁄ swtich ⁄ control switch  
for volume flow, differential pressure, filter  monitoring and 
liquid level detection, incl. connection set

F

  

Notice d’instruction

Convertisseur de mesure de pression ⁄  pressostat  
pour débit volumique, pression différentielle,  
contrôle de filtrage et détection de niveau de liquide,  
y compris kit de raccordement

r

  

Руководство по монтажу и обслуживанию

Измерительный преобразователь ⁄ реле давления ⁄  
реле контроля давления для объемного расхода,  
разности давлений, контроля работы фильтров и измерения 
уровня жидкости, вкл. комплект соединительных деталей

6000-3270-0000-1XX

  32700-2020  V110

    04  ⁄  2020

S+S REGELTECHNIK GMBH 
PIRNAER STRASSE 20 
90411 NÜRNBERG ⁄ GERMANY

FON  +49 (0) 911 ⁄ 5 19  47- 0 
FAX  +49 (0) 911 ⁄ 5 19  47- 70

[email protected] 
www.SplusS.de

Summary of Contents for Premasreg 716 Series

Page 1: ...rfassung incl Anschluss Set G Operating Instructions Mounting Installation Pressure measuring transducer swtich control switch for volume flow differential pressure filter monitoring and liquid level...

Page 2: ...12 20 4 6x1 5 6x1 5 112 112 M12 M12 98 98 50 126 90 112 20 4 112 20 4 112 20 4 112 20 4 M16x1 5 M16x1 5 112 112 M M 50 126 112 20 4 112 20 4 Geh use mit M12 Steckverbinder Housing with M12 connector B...

Page 3: ...achung F llstand einstellbar Messbereiche 10 100 einstellbar Druckart Differenzdruck Druckanschluss standardm ig mit Anschluss Stutzen aus Metall f r Druckschlauch 6 mm optional mittels Schnell Stecka...

Page 4: ...00 0060 7000 000 WS 03 Wetter und Sonnenschutz 200 x 180 x 150 mm aus Edelstahl V2A 1 4301 7100 0040 6000 000 DIP Schalter 4 ist nicht belegt PREMASREG 716x U W 3 Leiter Anschluss Schaltbild 1 2 3 230...

Page 5: ...ktionstypen Volumenstrom V k p V Volumenstrom in m3 h k k Faktor 1 3000 p Differenzdruck in Pa Differenzdruck p p p p Differenzdruck in Pa p h herer Druck p niedriger Druck Filterverschmutzung S 100 p...

Page 6: ...Nullpunktes Dies wird durch ein Dauerlicht der LED und im Display durch das Umschalten von AUTO 0 nach PROG 0 angezeigt Hinweis Durch Loslassen des Tasters w hrend des Countdowns Z hler 0 wird das Se...

Page 7: ...er zweiten Zeile wird die entsprechende Einheit z B Pa m3 h cm dargestellt In der dritten Zeile kann der Schaltzustand des Relais Kreis ausgef llt leer mit dem entsprechenden Set Wert abgelesen werden...

Page 8: ...lle Relais Volumenstrom Einstellung Schaltpunkt Relais 10 bis Messbereichsendwert in der eingestellten Einheit Typ 1 Differenzdruck Differenzdruck f r max Ausgangsignal 10V Einstellung Messbereichsend...

Page 9: ...e m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk rpern oder deren W rmestrom eingesetzt...

Page 10: ...ring fill level adjustable Measuring ranges 10 100 adjustable Type of pressure differential pressure Pressure connection equipped as standard with metal connection nozzles for pressure hose 6 mm optio...

Page 11: ...el V2A 1 4301 7100 0040 6000 000 DIP switch 4 is not assigned PREMASREG 716x U W 3 wire connection Schematic diagram 1 2 3 230V AC 24V AC DC PLC PC UB 24V AC DC Output pressure Pa 0 10V UB GND Pin ass...

Page 12: ...w in m3 h k K factor 1 3000 p Differential pressure in Pa Differential pressure p p p p Differential pressure in Pa p higher pressure p lower pressure Filter contamination S 100 p pFilter S Contaminat...

Page 13: ...oint calibration takes place This is indicated by continuous light of the LED and on the display by switching from AUTO 0 to PROG 0 Note When releasing the pushbutton during countdown counter 0 zero p...

Page 14: ...degree or level The second line shows the corresponding unit e g Pa m3 h cm In the third line the switching status of the relay circuit completed empty with the corresponding set value can be read If...

Page 15: ...tching threshold at volume flow rate Setting relay switchpoint 10 to measuring range end value in the selected measurement unit Type 1 Differential pressure Differential pressure for max output signal...

Page 16: ...ur products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed to their heat flow Direc...

Page 17: ...pression diff rentielle contr le de filtrage niveau de remplissage r glables Plages de mesure 10 100 r glable Type de pression Pression diff rentielle Prise de pression avec des embouts droits en m ta...

Page 18: ...2A 1 4301 7100 0040 6000 000 Interrupteur DIP n 4 n est pas affect PREMASREG 716x U W 3 fils raccordement Sch ma de raccordement 1 2 3 230V AC 24V AC DC PLC PC UB 24V AC DC Output pressure Pa 0 10V UB...

Page 19: ...1 3000 p pression diff rentielle en Pa Pression diff rentielle p p p p pression diff rentielle en Pa p pression plus lev e p pression moins lev e Encrassement du filtre S 100 p pFiltre S degr d encra...

Page 20: ...l cran Une fois le compte rebours termin l appareil effectue le calibrage du point z ro Ceci est indiqu par la DEL allum e en continu ainsi que par l cran qui passe du mode AUTO 0 en mode PROG 0 Atte...

Page 21: ...pression le degr d encrassement ou le niveau L unit correspondante est repr sent e dans la deuxi me ligne par ex Pa m3 h cm L tat de commutation du relais cercle plein vide peut tre lu dans la troisi...

Page 22: ...age relais point de commutation 10 jusqu la valeur de fin de plage de mesure dans l unit param tr e Type 1 pression diff rentielle Pression diff rentielle pour signal de sortie max 10 V R glage valeur...

Page 23: ...itement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus C...

Page 24: ...36 RL 5 1 5 24 2 8 24 0 10 1 24 1 3 10 100 6 6 20 50 C 7161 1000 5 7165 5000 25 1 0 1 C 10 000 1 c 10 c DIP 1 1 10 50 0 14 1 5 M 16 x 1 5 10 4 M12 12 A DIN EN 61076 2 101 30 RAL 9016 126 x 90 x 50 Tyr...

Page 25: ...mally Closed NO Normally Open free free free 45 1 2 3 7 6 5 4 9 8 11 10 12 1 2 3 4 5 6 7 8 9 10 11 12 UB 24V AC 15 36V DC Output pressure 0 10V Pa free UB GND free free COM Common NC Normally Closed N...

Page 26: ...C P1 P2 D P1 P2 E P1 P2 P1 P2 A B C D E Types de V k p V 3 k 1 3000 p p p p p p p S 100 p p S p p h p g h p 700 1300 3 g 9 81 2 DIP 1 1 0 DIP 2 DIP 3 0 MR default OFF default OFF default OFF MR MR ON...

Page 27: ...SET 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUT...

Page 28: ...P DOWN 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 3 limit DIP 3 OFF SEL...

Page 29: ...PREMASREG 716x 0 k 1 3000 k kS S kEBM PAPST kS S kZIEHL ABBEG kS S kGEBHARDT 0 7746 kS S kROSENBERG 0 7746 kS S 3600 kFL KT 0 3 3 1 3 4 2 3 5 10 10 10 100 10 1 10 10 10 100 10 2 10 0 100 3 700 1300 3...

Page 30: ...30 P P 10 ZVEI VDE EMV r 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Page 31: ...ity of our products as stated in our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat de nos connaissances au moment de la...

Page 32: ...32 PREMASREG 716x D G F r WS 03 Wetter und Sonnenschutz optional Weather and sun protection optional Protection contre les intemp ries et le soleil en option PREMASREG 716x LCD PREMASREG 716x Q LCD...