PREMASREG

®

 716x 

Rev.  2020 - V27  +  ID20 - V12 

The electronic 

PREMASREG

® 

716x

 pressure sensor and switch is equipped with measuring functions for volume flow, differential pressure, filter 

monitoring and liquid level detection based on pressure measurement in clean air. The devices with  a housing made from impact-resistant  
plastic, with cable gland or M12 connector according to DIN EN 61076-2-101 and with metal pressure port nozzles (quick connect optional) are  
fitted with one switching output, one continuous output and one backlit display for setting the switching point and displaying the ACTUAL values.  
The piezoresistive measuring element guarantees a high degree of reliability and accuracy. 

This pressure sensor is used in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale 
catering facilities, for filter monitoring and level measurement or for triggering frequency converters. The medium measured is air (non-precipitating), 
or other gaseous, non-aggressive, non-combustible media. It has a manual zero point pushbutton and an offset potentiometer for final value correction. 
Parameter entry is menu-based and is easy to perform using three buttons with the help of the display. 

The delivery includes the connection set 

ASD-06

 (2 m connection hose, two pressure port nipples, screws).

TECHNICAL DATA

Power supply:  

24 V AC ⁄ DC (± 10 %)  and  15...36 V DC 

Load resistance: 

R

L

 > 5 kOhm

Power consumption:  

< 1.5 VA  ⁄  24 V DC,  < 2.8 VA  ⁄  24 V AC

Output:  

0  -10 V 
1 changeover contact (24 V), 1 A ohmic load

Connection type:  

3-wire  connection

Measuring  function:  

Volume flow, differential pressure, filter monitoring, fill level 

 (adjustable)

Measuring ranges:  

10...100% 

 (adjustable)

Type of pressure:  

differential pressure

Pressure  connection:  

equipped as standard with metal connection 

nozzles

 for pressure hose Ø 6 mm 

(optionally with 

quick 

connect made from stainless steel for PVC  fabric pressure hose Ø 6 mm)

Medium:  

clean air and non-aggressive, non-combustible gases

Media  temperature:  

–20...+50 °C

Accuracy:   

Type 7161

 (1000 Pa):  typically   ± 5 Pa 

Type 7165

 (5000 Pa):  typically ± 25 Pa 

compared to the calibrated reference device

Sum of Lihysteresis:  

<  ± 1 % of final value (pressure)

Temp. drift values:  

± 0.1 %  ⁄ °C

Above-⁄ below-atmospheric pressure:  max.   ± 10000  Pa

Signal  filtering:  

switchable  1 s  ⁄  10 s  

(via DIP switches) 

and small value suppression < 1 %

Signal hysteresis:  

± 1 % or final value (pressure)  10 Pa ⁄ 50 Pa

Electrical connection:  

0.14 - 1.5 mm²,  via plug-in screw terminal

Cable connection: 

cable gland

, plastic  

(M 16 x 1.5; with strain relief, exchangeable, inner diameter 10.4 mm) 

or  

M12 connector

 (male, 12-pin, A-code) according to DIN EN 61076-2-101

Housing:  

plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced,  
with quick-locking screws (slotted ⁄ Phillips head combination),  
colour traffic white (similar to RAL 9016), cover for display is transparent!

Dimensions:  

126  x  90  x  50 mm    (Tyr 2)

Air  humidity:  

< 95 %  r. H.,  non-precipitating  air

Protection  type:  

IP 65

   (according to EN 60 529)  in the built-in state

Standards:  

CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU, 
according to EN 61326-1, according to EN 61326-2-3

Equipment:  

Display with illumination, 

three-line,  cutout  approx. 70 x 40 mm  (W x H),       

for displaying the 

volume flow, differential pressure, contamination degree 

or

 level

 and  

for setting the 

switchpoint, K factor, measuring range limits 

and other settings

K factor:  

1 to 3000 

 (adjustable) 

Units:  

m³ ⁄ s,    m³ ⁄ min,    m³ ⁄ h,    l  ⁄ s,    l  ⁄ min,    l  ⁄  h,    %,    cm 

 (adjustable) 

Max. value displayed:  

999999

ACCESSORIES

 

see table

Summary of Contents for Premasreg 716 Series

Page 1: ...rfassung incl Anschluss Set G Operating Instructions Mounting Installation Pressure measuring transducer swtich control switch for volume flow differential pressure filter monitoring and liquid level...

Page 2: ...12 20 4 6x1 5 6x1 5 112 112 M12 M12 98 98 50 126 90 112 20 4 112 20 4 112 20 4 112 20 4 M16x1 5 M16x1 5 112 112 M M 50 126 112 20 4 112 20 4 Geh use mit M12 Steckverbinder Housing with M12 connector B...

Page 3: ...achung F llstand einstellbar Messbereiche 10 100 einstellbar Druckart Differenzdruck Druckanschluss standardm ig mit Anschluss Stutzen aus Metall f r Druckschlauch 6 mm optional mittels Schnell Stecka...

Page 4: ...00 0060 7000 000 WS 03 Wetter und Sonnenschutz 200 x 180 x 150 mm aus Edelstahl V2A 1 4301 7100 0040 6000 000 DIP Schalter 4 ist nicht belegt PREMASREG 716x U W 3 Leiter Anschluss Schaltbild 1 2 3 230...

Page 5: ...ktionstypen Volumenstrom V k p V Volumenstrom in m3 h k k Faktor 1 3000 p Differenzdruck in Pa Differenzdruck p p p p Differenzdruck in Pa p h herer Druck p niedriger Druck Filterverschmutzung S 100 p...

Page 6: ...Nullpunktes Dies wird durch ein Dauerlicht der LED und im Display durch das Umschalten von AUTO 0 nach PROG 0 angezeigt Hinweis Durch Loslassen des Tasters w hrend des Countdowns Z hler 0 wird das Se...

Page 7: ...er zweiten Zeile wird die entsprechende Einheit z B Pa m3 h cm dargestellt In der dritten Zeile kann der Schaltzustand des Relais Kreis ausgef llt leer mit dem entsprechenden Set Wert abgelesen werden...

Page 8: ...lle Relais Volumenstrom Einstellung Schaltpunkt Relais 10 bis Messbereichsendwert in der eingestellten Einheit Typ 1 Differenzdruck Differenzdruck f r max Ausgangsignal 10V Einstellung Messbereichsend...

Page 9: ...e m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk rpern oder deren W rmestrom eingesetzt...

Page 10: ...ring fill level adjustable Measuring ranges 10 100 adjustable Type of pressure differential pressure Pressure connection equipped as standard with metal connection nozzles for pressure hose 6 mm optio...

Page 11: ...el V2A 1 4301 7100 0040 6000 000 DIP switch 4 is not assigned PREMASREG 716x U W 3 wire connection Schematic diagram 1 2 3 230V AC 24V AC DC PLC PC UB 24V AC DC Output pressure Pa 0 10V UB GND Pin ass...

Page 12: ...w in m3 h k K factor 1 3000 p Differential pressure in Pa Differential pressure p p p p Differential pressure in Pa p higher pressure p lower pressure Filter contamination S 100 p pFilter S Contaminat...

Page 13: ...oint calibration takes place This is indicated by continuous light of the LED and on the display by switching from AUTO 0 to PROG 0 Note When releasing the pushbutton during countdown counter 0 zero p...

Page 14: ...degree or level The second line shows the corresponding unit e g Pa m3 h cm In the third line the switching status of the relay circuit completed empty with the corresponding set value can be read If...

Page 15: ...tching threshold at volume flow rate Setting relay switchpoint 10 to measuring range end value in the selected measurement unit Type 1 Differential pressure Differential pressure for max output signal...

Page 16: ...ur products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed to their heat flow Direc...

Page 17: ...pression diff rentielle contr le de filtrage niveau de remplissage r glables Plages de mesure 10 100 r glable Type de pression Pression diff rentielle Prise de pression avec des embouts droits en m ta...

Page 18: ...2A 1 4301 7100 0040 6000 000 Interrupteur DIP n 4 n est pas affect PREMASREG 716x U W 3 fils raccordement Sch ma de raccordement 1 2 3 230V AC 24V AC DC PLC PC UB 24V AC DC Output pressure Pa 0 10V UB...

Page 19: ...1 3000 p pression diff rentielle en Pa Pression diff rentielle p p p p pression diff rentielle en Pa p pression plus lev e p pression moins lev e Encrassement du filtre S 100 p pFiltre S degr d encra...

Page 20: ...l cran Une fois le compte rebours termin l appareil effectue le calibrage du point z ro Ceci est indiqu par la DEL allum e en continu ainsi que par l cran qui passe du mode AUTO 0 en mode PROG 0 Atte...

Page 21: ...pression le degr d encrassement ou le niveau L unit correspondante est repr sent e dans la deuxi me ligne par ex Pa m3 h cm L tat de commutation du relais cercle plein vide peut tre lu dans la troisi...

Page 22: ...age relais point de commutation 10 jusqu la valeur de fin de plage de mesure dans l unit param tr e Type 1 pression diff rentielle Pression diff rentielle pour signal de sortie max 10 V R glage valeur...

Page 23: ...itement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus C...

Page 24: ...36 RL 5 1 5 24 2 8 24 0 10 1 24 1 3 10 100 6 6 20 50 C 7161 1000 5 7165 5000 25 1 0 1 C 10 000 1 c 10 c DIP 1 1 10 50 0 14 1 5 M 16 x 1 5 10 4 M12 12 A DIN EN 61076 2 101 30 RAL 9016 126 x 90 x 50 Tyr...

Page 25: ...mally Closed NO Normally Open free free free 45 1 2 3 7 6 5 4 9 8 11 10 12 1 2 3 4 5 6 7 8 9 10 11 12 UB 24V AC 15 36V DC Output pressure 0 10V Pa free UB GND free free COM Common NC Normally Closed N...

Page 26: ...C P1 P2 D P1 P2 E P1 P2 P1 P2 A B C D E Types de V k p V 3 k 1 3000 p p p p p p p S 100 p p S p p h p g h p 700 1300 3 g 9 81 2 DIP 1 1 0 DIP 2 DIP 3 0 MR default OFF default OFF default OFF MR MR ON...

Page 27: ...SET 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUT...

Page 28: ...P DOWN 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 3 limit DIP 3 OFF SEL...

Page 29: ...PREMASREG 716x 0 k 1 3000 k kS S kEBM PAPST kS S kZIEHL ABBEG kS S kGEBHARDT 0 7746 kS S kROSENBERG 0 7746 kS S 3600 kFL KT 0 3 3 1 3 4 2 3 5 10 10 10 100 10 1 10 10 10 100 10 2 10 0 100 3 700 1300 3...

Page 30: ...30 P P 10 ZVEI VDE EMV r 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Page 31: ...ity of our products as stated in our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat de nos connaissances au moment de la...

Page 32: ...32 PREMASREG 716x D G F r WS 03 Wetter und Sonnenschutz optional Weather and sun protection optional Protection contre les intemp ries et le soleil en option PREMASREG 716x LCD PREMASREG 716x Q LCD...

Reviews: