Process interfacing via an automation system (PLC, PC)
9.1 Integration via onboard PROFINET IO
SIMATIC MV500
106
Operating Instructions, 06/2018, C79000-G8976-C494-01
8.
In the next dialog, click the "Continue" button to start the installation.
At the end of the installation, a message appears indicating that the installation was
successful.
9.
Click the "Finish" button and restart the TIA Portal.
Result: Your hardware catalog in the TIA Portal has now been updated and the reader is
included. You can find the optical readers under the following path in the hardware catalog:
"Additional field devices > PROFINET IO > Ident systems > SIEMENS AG > SIMATIC Code
Reading Systems > MV500".
Assigning PROFINET device names
The optical reader detects the transmission speed of PROFINET automatically. PROFINET
operates in 100 Mbps full duplex mode.
To assign the reader a unique PROFINET device name, follow these steps:
1.
Open the TIA Portal with "Start > All Programs > Siemens Automation > TIA Portal Vxx".
2.
Create a new project.
3.
Change to the Project view.
4.
Using the project tree, insert an S7 controller in the project using the "Add new device"
menu command.
The device view opens and the S7 controller is displayed.
5.
Drag the optical reader from the hardware catalog into the project.
6.
Switch to the network view and connect the reader to the S7 controller.
7.
Optional: Enter a PROFINET device name in the properties of the reader in the tab
"General" > Parameter group "PROFINET interface [X1] > Ethernet addresses",
"PROFINET" area.
8.
Right-click on the reader.