Product Overview
1-15
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
1.6
ET 200X with SITOP power
Function
SITOP-mode power supply unit for ET 200X.
It integrates into the ET 200X without additional wiring and supply the power for
electronics/sensors and/or the load voltage. Response to faults is parameterizable
(restart or shutdown following a short circuit on the output side).
Note
SITOP power 24V/10A must always be installed in the rightmost slot of the
ET 200X.
If a SITOP power module is installed on a BM 143-DESINA or
BM 141-ECOFAST, do not use the DESINA hybrid cable to supply power
(power is supplied by the SITOP power). In this case the DESINA hybrid cable
is used only for connection to PROFIBUS-DP.
Do not loop through the power supply from a BM 143-DESINA or
BM 141-ECOFAST with SITOP power.
Configuration of ET 200X with SITOP power 24V/10A (example)
SITOP power
X1
X2
X3
X4
24 VDC
BF
ON
SF
X1
X2
X3
X4
X1
X2
X3
24 VDC
LOAD 2L+
TEMP >
ELECTRONIC/SENSOR 1L+
Figure 1-9
Configuration of ET 200X with SITOP power (Example)
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...