Technical Specifications
7-26
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Dimensions and weight
Dimensions
W
H
D (mm)
175
180
110
Weight
Approx. 650 g
Module-specific data
Baud rate
9.6/19.2/45.45/93.75/
187.5/500 kbps
1.5/3/6/12 Mbps
Bus protocol
PROFIBUS-DP
FREEZE compatibility
Yes
SYNC compatibility
Yes
Number of channels
8 digital inputs and
outputs
8 functional
inputs (diagnostics
inputs or inputs with
NC functionality)
Cable length
Unshielded
Max. 30 m
Manufacturer identification
809A
H
Voltages, currents, potentials
Non-switched rated load
voltage (NS)
Max. perm. power input
from load
Reverse polarity
protection
Short-circuit protection
24 VDC
Up to 40
C 10 A;
Up to 55
C 8
A
No
No
Switched rated load voltage
(NS)
Max. perm. power input
from load
Reverse polarity
protection
24 VDC
Up to 40
C 10 A;
Up to 55
C 8
A
No
Maximum number of inputs
driven simultaneously
all installed positions
max. 55
C
8
Aggregate current of out-
puts
All installation positions
To 20
C
To 50
C
To 55
C
Max. 10 A
Max. 6 A
Max. 5 A
Electrical isolation
Between channels and
backplane bus
No
Between channels
No
Between load voltages
No
Between load voltage
and all other circuitry
No
Between
PROFIBUS-DP and all
other circuitry
Yes
Permissible potential diffe-
rence
Between different
circuits
75 VDC, 60 VAC
Insulation tested with
500 VDC
Power loss of module
Typ. 3.5 W
Status, alarms, diagnostics
Status display
Yellow LED per
channel
Indicator for functional input
Yellow/red LED
per channel
Alarms
Diagnostic interrupt
Diagnostic functions
Configurable
Group error
Red LED (SF)
Status indicator
Green LED (RUN)
Indicator for
non-switched load
voltage
Green LED
(DC 24V-NS)
Indicator for switched
load voltage
Green LED
(DC 24V-S)
Reading diagnostic
information
Possible
Sensor supply outputs
Outputs
Output current
Short-circuit protection
8
Up to 40
C
max. 1 A;
Up to 55
C
max. 0.8 A
Yes, electronic
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...