Technical Specifications
7-6
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Dimensions and weight
Dimensions
W
H
D (mm)
134
110
55
Weight
Approx. 500 g
Module-specific data
Baud rate
9.6/19.2/93.75/187.5
/500 kbps
1.5/3/6/12 Mbps
Bus protocol
PROFIBUS-DP
FREEZE compatibility
Yes
SYNC compatibility
Yes
Number of inputs
8
Cable length
Unshielded
Max. 30 m
Manufacturer identification
803D
H
Voltages, currents, potentials
Rated supply voltage for
electronic components and
sensors 1L+
Max. perm. current for
electronic components
and sensors
Reverse polarity
protection
Short circuit protection
24 VDC
Up to 40
C 1 A;
Up to 55
C 0.8 A
Yes
Yes, electronic
Rated load voltage 2L +
Reverse polarity
protection
24 VDC
No
Max. perm. power input
from load
Up to 40
C 10 A;
Up to 55
C 8 A
Maximum number of inputs
driven simultaneously
All installation positions
To 55
C
8
Electrical isolation
Between channels
Between load voltage
and all other circuit
components
Between
PROFIBUS-DP and all
other circuit
components
No
Yes
Yes
Permissible potential diffe-
rence
Between different
circuits
75 VDC, 60 VAC
Insulation tested with
500 VDC
Power input
From supply voltage
1L+
Max. 180 mA
Power loss of module
Typ. 3.5 W
Status, alarms, diagnostics
Status display
Green LED per
channel
Alarms
Diagnostic interrupt
Diagnostic functions
Group error
PROFIBUS-DP bus
monitoring
Monitoring of the
electronics power
supply
Load voltage monitor
Reading diagnostic
information
Configurable
Red LED (SF)
Red LED (BF)
Green LED (ON)
Green LED (24VDC)
Possible
Sensor supply outputs
Outputs
Output current*
Short circuit protection
4
Up to 40
C
max. 0.9A;
Up to 55
C
max. 0.7A
Yes, electronic
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...