Commissioning and Diagnostics
5-37
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
5.6.6
ID-specific diagnosis
Definition
The ID-specific diagnosis states whether or not the modules of the ET 200X are
defective. The module diagnosis begins as of byte 6 and comprises 3 bytes.
Module diagnosis
The module diagnosis for the ET 200X is structured as follows:
Byte 6
7
0
Bit no.
Length of the module diagnosis
including byte 6 (= 3 bytes)
Byte 7
Entry for ET 200X
Entry for expansion module 1
Entry for expansion module 2
Entry for expansion module 3
Entry for expansion module 4
Byte 8
Entry for expansion module 5
Entry for expansion module 6
Entry for expansion module 7
Code for module diagnosis
0 1 0 0 0 0 1 1
7 6 5 4
1
0
2 1
3
Entry for I/O section of basic module
Legend for the entry for a module:
Bit is set when
- a module is pulled
- an unconfigured module is inserted
- access to a module is not possible
- a module reports a diagnostic interrupt
Bit no.
Bit no.
See legend
Figure 5-9
Structure of ID-specific diagnosis for ET 200X
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...