General Technical Specifications
6-6
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
6.3
Mechanical and climatic environmental conditions
Shipping and storage conditions
The ET 200X distributed I/O device exceeds the requirements of EC 61131-2 with
regard to transport and storage conditions. The following figures are valid for
modules that have been transported or stored in their original packaging.
Type of condition
Permissible range
Free fall
BM/EM/frequency converter:
1 m
Motor starter:
0.35 m
Temperature
BM/EM, except the pneumatic module:
from –40
C to +70
C
Pneumatic module: from –30
C to +70
C
Temperature variation
20 K/h
Air pressure
From 1080 to 660 hPa (corresponds to an
altitude of -1000 to 3500 m)
Relative humidity
From 5 to 95 %, without condensation
Climatic environmental conditions
The following climatic environmental conditions apply:
Environmental conditions
Operating ranges
Remarks
Temperature
From 0 to 55
C
For horizontal installation; not
for pneumatic components
From 0 to 50
C
For horizontal installation of
pneumatic components
From 0 to 40
C
For all other installation posi-
tions
Temperature variation
10 K/h
Relative humidity
From 5 to 100 %
Air pressure
From 1080 to 795 hPa
Corresponds to an altitude of
-1000 to 2000 m
Contaminant concentration
SO
2
: < 0.5 ppm;
rel. humidity < 60 %, no moisture con-
densation
H
2
S: < 0.1 ppm;
rel. humidity < 60 %, no moisture con-
densation
Test:
10 ppm; 4 days
1 ppm; 4 days
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...