Commissioning and Diagnostics
5-51
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Byte x+4 to x+7 (x+10) for diagnosis of ET 200X
If byte x+2 contains the slot number 02, this indicates that a basic module is
generating diagnostic messages. These diagnostic messages are contained in
bytes x+4 to x+7 (x+10).
Table 5-22 gives you the meaning of bytes x+4 to x+7 (x+10) when the following
basic modules are used:
Basic module
MLFB
BM 141 DI 8
DC 24V
6ES7 141-1BF11-0XB0
6ES7 141-1BF12-0XB0
BM 141 DI 8
DC 2 ECOFAST
6ES7 141-1BF00-0AB0
6ES7 141-1BF01-0AB0
BM 141 DI 8
DC 24V
ECOFAST DIAG
6ES7 141-1BF40-0AB0
BM 142 DO 4
DC 24V/2A
6ES7 142-1BD21-0XB0
6ES7 142-1BD22-0XB0
BM 143-DESINA FO
6ES7 143-1BF00-0XB0
BM 143-DESINA RS485
6ES7 143-1BF00-0AB0
Table 5-22 Bytes x+4 to x+10 in the diagnosis of ET 200X
Byte
Bit
Meaning
Remarks
0
Error
1:
0:
Error
No error
1
Internal error
Cause of fault is in BM
2
External error
Cause of fault is in configuration of ET 200X
3
Module fault
BM cannot access one or more plugged-in
modules
x+4
4
Load voltage
1:
0:
Error
No error
5
not assigned
–
6
Parameters not assigned to module
–
7
Parameter assignment
1:
0:
Error
No error
x+5
0 to 7
1B
H
Fixed
x+6
0 to 7
not assigned
–
x+7
0 to 7
not assigned
–
x+8
0 to 7
Module ID
55
H
for basic module
x+9
0 to 7
08
H
Length of channel-specific diagnosis
x+10
0 to 7
08
H
Fixed
x+11
to
x+19
0 to 7
not assigned
–
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...