Wiring
4-26
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Wiring of M12 coupler plug for digital inputs (DESINA/ECOFAST)
To connect the digital inputs, you require:
A 5-pin, M12 coupler plug, possibly integrally molded
A flexible 4- or 5-core copper cable with a core cross-section of
0.75 mm
2
Wire the coupler plug in accordance with the pinout table below. You can find the
pinout of sockets X1 to X8 which are used for the outputs on the
ET 200X-DESINA/ET 200X-ECOFAST as of Section 7.5.
Connecting digital outputs (DESINA):
Your parameter settings are as follows:
Channel type (pin 4): digital output
Input functionality (pin 2): diagnostic input
Table 4-9
Pinout of the coupler plug for digital outputs (DESINA)
Pin
Assignment for digital
output (DESINA)
View of coupler plug
(wiring side)
1
24 V power supply for
diagnostics input*
Digital output (DE-
SINA)
2
Diagnostic input
SINA)
3
Chassis ground, load
supply
1
2
3
5
4
Output signal to
DESINA actuator
4
5
not assigned
*
Made available by the ET 200X-DESINA for the diagnostics input
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...