Technical Specifications
7-86
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Table 7-41 Parameters of analog inputs, Fortsetzung
Expansion modules with
Area affected
Default
Range
Parameters
All
Trigger for
hardware
interrupt
Upper limit
value
Lower limit
value
From 32511 to
–32512
From –32512
to 32511
–
–
Channel
1
For optimum interference suppression of the analog modules as a function of the system frequency
(at 50 Hz, 20 msec reset time; at 60 Hz, 16.7 msec reset time)
Table 7-42 Parameters of analog outputs
Expansion
modules with
AOs
Parameters
Range
Default
Area affected
All
Format
SIMATIC S7
format/
SIMATIC S5
format
SIMATIC S7
format
Expansion module
All
Enable
Diagnostic
interrupt
Yes/no
No
Expansion module
All
Diagnosis
Group
diagnosis
Yes/no
No
Channel
All
Behavior upon
CPU STOP
Set substitute
value/ maintain last
value/no current or
voltage
No current or
voltage
Channel
All
Substitute value*
0/1
0
Channel
*
Substitute values are current or voltage values that are output upon STOP of the master CPU by the
module with analog outputs to the process.
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...