Commissioning and Diagnostics
5-36
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
5.6.4
Master PROFIBUS address
Definition
The PROFIBUS address of the DP master is stored in diagnostics byte 3: this is
the master
which assigned parameters to the DP slave
which has read and write access to the DP slave
FF
H
in byte 3
If the value FF
H
is defined as the master PROFIBUS address in byte 3, the DP
slave has not been parameterized by the DP master.
5.6.5
Manufacturer identification
Definition
A code is stored in the manufacturer ID that describes the type of the DP slave.
Manufacturer identification
Table 5-19 Structure of the manufacturer ID (Byte 4, 5) ET 200X
Byte 4
Byte 5
Manufacturer ID for
80
H
3D
H
BM 141 DI 8 x DC 24V
80
H
D2
H
BM 141 DI 8 x DC 24V ECOFAST
80
H
D3
H
BM 141 DI 8 x DC 24V EDOFAST DIAG
80
H
3C
H
BM 142 DO 4 x DC 24V/2A
80
H
9A
H
BM 143-DESINA FO
80
H
9A
H
BM 143-DESINA RS485
Summary of Contents for SIMATIC ET 200X
Page 8: ...Preface viii ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 20: ...Contents xx ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 40: ...Product Overview 1 20 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 58: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 80: ...Installation 3 22 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 124: ...Configuration Options 2 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 328: ...Order Numbers A 10 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 348: ...Dimesioned Drawings and Pinouts C 18 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...
Page 362: ...Index Index 8 ET 200X Distributed I O Device EWA 4NEB 780601602 06 ...