15 Operating Parameters
15.6 Administrative
358
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
15.6.2
Ethernet Communication
Parameter
Default Setting
Setting Range
Communication Ethernet
IP address
1)
192.168.0.55
Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0
Any
Default gateway
1)
192.168.0.1
Any
Ethernet switch on
no
no
yes
Enable SNMP
no
no
yes
Bus protocol
Modbus TCP
-none-
Modbus TCP
IEC 61850
Both
Protocol Modbus TCP
Use a user-port number
2)
no
no
yes
User-port number
2)
(can only be set when
Use a user-port
number
is parameterized with
yes
)
10 000
10 000 to 65 535
Access rights for user port
(can only be set when
Use a user-port
number
is parameterized with
yes
)
Full
Full
Read only
Access rights for port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 (* 100 ms)
0 s = none
100 ms to 6 553 400 ms
Modbus TCP/RTU Gateway
(Condition: The Modbus RTU Master protocol must have been selected under serial communication.)
Activated
no
no
yes
Unit ID of this device
255
1 to 255